The cable tray load is divided into static load, dynamic load and additional load.
Static load refers to the type, number and outer diameter weight/unit length of the cables laid in the cable tray, which are listed and counted according to the different routes of cable laying.
Dynamic load refers to the weight of construction and maintenance personnel during the installation and maintenance of the cable tray. For light cable trays, dynamic load is generally not considered, that is, people are not allowed to stand (walk) on the bridge. If standing is required, the span should be appropriately reduced.
Additional load refers only to the load formed by ice, snow, wind and electromagnetic force outdoors. It is related to the natural meteorological conditions of the area where the installation site is located and the properties of the charged body. It should be calculated according to various conditions in the design.
Expansion and contraction problem
Due to changes in ambient temperature, steel cable trays will expand and contract with heat. Outdoor cable trays are greatly affected by temperature. For example, if the highest ambient temperature is 40℃ and the lowest temperature is -20℃, the maximum contraction of the cable tray is calculated as follows:
Δt=11.2 ×10-6×60deg(degrees)×1000mm
From this, we can conclude that:
When the temperature difference is 60℃, Δι =0.672mm/m
When the temperature difference is 50℃, Δι =0.560mm/m
When the temperature difference is 40℃, Δι =0.448mm/m
In engineering design, expansion joints should be considered for straight cable trays. The spacing of expansion joints is recommended to be determined as follows:
When the temperature difference is 40℃, it is 50m;
When the temperature difference is 50℃, it is 40m;
When the temperature difference is 60℃, it is 40m;